Connect an AREARAE to the Safety Suite
Connect an AreaRAE to RAELink 3 via the PTM protocol. The RAELink 3 is connected to the Safety Suite.
-
Press-hold the RAELink3 Power button to turn the device on.
-
SET THE NETWORK ID: Press-hold
and the N/- buttons simultaneously to enter Programming mode.
-
Press Y/+ to change the Network ID (pick a value from 1-9999).
-
Press-hold
to see the Save option, and then press Y/+ to save the new Network ID.
-
SET THE HOST MODE: Press N/- to view the option to change the Operation Mode (OP).
-
Press Y/+ to scroll to the diverse options: Repeater, Remote, Host. For this operation, we will select HOST mode.
-
Press-hold
to confirm and save the selected OP Mode. The HOST OP Mode and NetID will display on the screen as follows.
-
Go to your AREARAE (Plus or Pro) device and Press-hold the power button
to turn it on.
-
Press-hold
and the N/- buttons simultaneously to get to the Setup mode.
-
Select Power ON, change your Network ID to match the RAELink 3, and set the Unit ID to a unique number between 1 and 64.
-
Tap the Back option until you save the changes and get to the Home Screen.
-
Scroll through the menu with the N/- button until you reach the ISM page and confirm that your Network ID matches the RaeLink 3. Then, set a UNIT ID.
-
CONNECTING THE RAELINK 3 TO THE COMPUTER: The RAELink 3 uses a special ATEN adapter to connect it to the PC’s USB port.
-
ATEN Cable: If this is your first time connecting your RAELink 3 to this PC, download the driver from here: https://www.aten.com/us/en/supportcenter/info/downloads/?action=display_product&pid=575
-
Open Device Manager on Microsoft Windows. Scroll down to Ports and confirm that your driver is installed. Verify that the COM port is COM6.
-
In Safety Suite go to Sites > Your Site > Gateways (Tab) > Your Gateway
-
Expand the PTM protocol and select it.
-
Select the port where the driver is installed (check the Device Manager page).
-
Select the Unit ID to match the Unit ID on AreaRAE.
-
Click START, and then click UPDATE.
-
Go to the Safety Suite Utility and verify your PTM connection on the COM6 port you selected.
-
Go to the Dashboard on Safety Suite and switch to Real Time Dashboard. Make sure you see the AreaRAE connected in the Safety Suite.